Who this is for
-
Step 1: Translate the request into the words vendors quote in
-
Step 2: Check the listing before you check the price
-
Step 3: Read the lifetime number as a test condition, not a promise
-
Step 4: Cost the controls on their own line
-
Step 5: Build the total-cost line, not the unit-price line
-
Step 6: Ask where the replacement part ships from
-
Step 7: Get the warranty terms and the claim path in writing
-
Notes and common mistakes
I approve lighting purchase orders for a living. Six years, three facilities, about $240,000 a year in fixtures, controls, and replacement parts. Before that I was the guy who got handed a quote and told to just get it ordered — which is how I learned that the expensive part of a lighting decision almost never shows up on the quote itself.
Here is the checklist I actually run. Not the version I would put in a written policy — the working version. Seven steps, roughly 90 minutes per project when vendors cooperate, and it has caught something worth fixing on maybe a third of the bids I have run it against.
Who this is for
If you are buying commercial or institutional lighting — warehouse high-bays, parking lot poles, office troffers, downlights, ceiling spotlights, or a grand chandelier for the lobby — and the fixture has to still be working in ten years, this applies. It works whether you are bidding three vendors or extending an existing contract. It even works when you are buying from a single manufacturer such as Acuity Brands Lighting, Inc., because half of these checks are about documentation, not competition.
Two things it won't do. It won't tell you which brand to buy, and it won't replace a physical mock-up. Everything else, it covers.
Step 1: Translate the request into the words vendors quote in
Most bid confusion I deal with is naming confusion, not pricing confusion. Three examples that come up constantly:
Flood light. People ask why it is called a flood light, and the honest answer is that the name predates the engineering. Early floodlights were reflector-and-lamp units with no lens — they literally flooded an area with a broad wash of light. Spotlights had lenses or shaped reflectors that concentrated the beam. The technology changed; the vocabulary didn't. Today the same phrase covers everything from a tight accent unit to a 120-degree wash, so if your RFQ just says flood light, you will get six different beam distributions and six prices that look comparable but aren't.
Ceiling spotlight. In a spec sheet this is an accent luminaire with a defined narrow beam — usually somewhere between 10 and 40 degrees — and it does a different job than a downlight. Vendors will quote them interchangeably if you let them.
Grand chandelier. The word comes from the Old French chandelle, candle, and it still describes a decorative multi-source luminaire more than a photometric category. Decorative fixtures are where the documentation gets thin — plenty of them have never been through an LM-79 test. That is fine in a private office. In a publicly funded lobby it can be a red flag at inspection or a rebate denial.
The checkpoint: before you send anything out, you should have a fixture schedule listing catalog number, wattage, delivered lumens, CCT, CRI, beam distribution or IES photometric file, control type, mounting, finish, and quantity. If two vendors come back with numbers you cannot line up side by side, the schedule is the problem. Fix it before you fix the price.
Step 2: Check the listing before you check the price
This takes ten minutes and eliminates about a third of the cheap options before you waste any more time on them.
- UL 1598 for the complete luminaire, UL 8750 for the LED driver and control components.
- DesignLights Consortium (DLC) listing on the Solid-State Lighting Qualified Products List. This is the one that gates utility rebates. The QPL is revised on a rolling basis — I pulled the current list on January 8, 2025 for our Q1 order, and two catalog numbers from an earlier bid had dropped off. Confirm your exact model number, not the product family.
- ANSI C136.10 locking-type receptacle if you are buying pole-mounted fixtures with a photocontrol. Skip this and you may be locked into one manufacturer's photocontrol part for the life of the pole.
- FCC Part 15 on the driver, especially for anything going into a space with sensitive equipment.
On rebates: I am not going to quote you a number, because rebate levels vary by utility and get reset every year. What I will say is that the rebate is a line item in your total cost whether or not you remembered to claim it, and I have watched an $800 rebate claim erase what looked like a losing bid. Verify the current program in writing before you build it into anything.
Step 3: Read the lifetime number as a test condition, not a promise
A 50,000-hour rating is a projection, not a warranty, and it depends entirely on the conditions it was measured under. What you want is LM-80 test data on the LED package, TM-21 extrapolation of that data, and the drive current and case temperature the extrapolation assumes.
The practical question is the one nobody asks: at what ambient temperature? A warehouse ceiling in July is not a 25-degree test chamber — it is closer to 45 or 50 degrees at the fixture. Ask for the LM-80 case temperature and compare it against your reality. If the vendor cannot produce the LM-79 absolute photometry report — not just the IES file, the report — that is your answer about how seriously the numbers were prepared.
L70 versus L90 matters too. L70 means 30 percent of the light is gone. On a task-lit production floor, that 30 percent is the difference between passing and failing a light level target, and you will be arguing about it in year seven.
Step 4: Cost the controls on their own line
Controls are where a cheap bid hides, because they are hard to compare and easy to bundle into one number.
Break out: sensor type and coverage, dimming protocol (0-10V, DALI, or wireless), whether the sensor is integral or remote, and whether the photocontrol is field-replaceable.
On photocontrols specifically, ask about the dark-to-light ratio. A dusk-to-dawn photocontrol has two thresholds — one light level where it switches on, a higher one where it switches off. The gap between them is what keeps a parking lot from dropping into darkness at 2 a.m. because headlights swept the sensor, or clicking on at noon during a storm. A control with a narrow ratio will do both. Ask for the ratio, and ask what happens when lightning hits.
The step most teams skip: whether the photocontrol is field-replaceable. A $40 part that swaps in ten minutes is a no-brainer. A sealed unit that has to go back to the factory means a bucket truck, two technicians, and a $1,100 invoice every time one fails — and on a 60-pole lot, something is always failing.
Step 5: Build the total-cost line, not the unit-price line
Same spreadsheet for every bid, same columns: fixture price, controls, freight, installation labor, lift rental, commissioning, rebate credit, expected replacement parts over ten years, disposal of the old fixtures. Then look at the bottom right cell.
A real one from Q2 2024. Bid A came in at $18,400 with field-replaceable photocontrols and a six-week lead time. Bid B came in at $16,900 with sealed photocontrols, freight excluded, and an eleven-week lead. The freight was $620. The first sealed control failure cost $1,100 in lift rental plus labor, and we had two in the first fourteen months. We also missed a site inspection date because of that eleven-week lead, which cost us nothing on paper and a lot in the relationship with the building owner.
I want to be honest about the scoreboard, because this is where I usually get accused of being the guy who always picks the expensive option. Over roughly 140 lighting POs, the higher bid has won on total cost more often than not — but not always. Twice, the cheap bid was genuinely the better buy, and I only knew it because the numbers were laid out in the same columns. The framework matters more than the instinct.
Step 6: Ask where the replacement part ships from
Everyone negotiates the fixture price. Almost nobody negotiates the parts channel, and that is the one you will still be dealing with in year six.
Ask three questions and get the answers in writing: which distribution center ships my replacement parts, what is the standard lead time on a driver or a photocontrol, and what is the process for ordering one without a PO amendment. Manufacturers with US production — the Acuity Brands sites in Crawfordsville, Indiana and Conyers, Georgia are the examples I know best — can often turn a part around faster than an import path, but geography only helps if the part is stocked and the lead time is documented.
I got burned on this exactly once, in 2022, on a verbal you will be fine. The fixture was correct. The part took five weeks and we had a parking structure running at half output for most of it. Verbal commitments on lead time are worth nothing. Written ones are worth a lot.
Step 7: Get the warranty terms and the claim path in writing
A ten-year warranty with no claim path is a marketing document. What I need on one page:
- Who I call, and the response time commitment in business hours.
- What is excluded. Labor, lift, freight, water ingress from a failed gasket, and voltage events are the usual carve-outs — and they are usually the entire cost of the failure.
- Whether the replacement ships before or after the failed unit is returned. In an occupied building, that answer matters more than the warranty length.
- The price validity window on the quote. Freight and aluminum move. Thirty days is normal, sixty is good, ninety gets a phone call.
Notes and common mistakes
Mock up one fixture before you release the PO. Hang it, wait for dark, walk the space with a meter. Check for flicker on a phone camera at a slow shutter speed — it shows up there long before it shows up in complaints. Watch the photocontrol switch at dusk. It is a two-hour investment, and it is the only step that has ever caught a mistake the paperwork missed.
Do not accept equivalents without a written side-by-side. Lumen output, wattage, CCT, CRI, beam, listing, and warranty, on one line. An equivalent that is 900 lumens dimmer is not an equivalent, it is a change order.
Do not mix fixtures and controls into one bundled number. The moment you do, you cannot bid it out again and you cannot compare it to anything.
Do not build a rebate into the budget before the QPL listing is confirmed. Listings change. Budgets do not.
Do not put decorative and functional fixtures on the same RFQ line. A grand chandelier and a ceiling spotlight have different failure modes, different documentation, and different buyers. Splitting them out costs you nothing.
Bottom line: this list takes about an hour and a half. The bad decision it prevents costs about a month — usually right when you can least afford it.